Heat Exchanger Integrity Test (HITMAN™)

Heat Exchanger Integrity Test (HITMAN™)

Heat Exchanger Integrity Test (HITMAN™)

Info
The Heat Exchanger Integrity Test is a Premier Services feature. It left beta in version 3.6.5. This article is for service technicians.

The Heat Exchanger Integrity Test, also called HITMAN™, is a quick test that screens each cell of a furnace heat exchanger. A hot-wire anemometer sits in the cell and a clamp meter reads blower current. The app reports whether the air in that cell moved when the blower started.

The test tells you which cell to inspect. It does not replace a heat exchanger inspection. Follow AHRI Guideline X (Induced Draft Furnace Heat Exchanger Inspection) for the full procedure.

What You'll Need

  • An active Premier Services subscription. See the Guide to measureQuick's Premier Services.
  • measureQuick version 3.6.5 or later.
  • A Testo 405i hot-wire anemometer.
  • A supported Bluetooth clamp meter to read blower current. Supported meters: Testo 770-3, UEi DL599, UEi HAC, CPS VOLT-100, Redfish iDVM550, Fieldpiece SC480 and SC680, and the Yellow Jacket YJACK AMP current probe. Jim used a Testo 770-3 in his demonstration.
  • Access to the opening of each heat exchanger cell. In Jim Bergmann's demonstration the burner assembly is removed.
  • A way to turn the blower on and off by itself.

Follow the furnace manufacturer's instructions and your company's safety procedures when you remove the burner assembly.

What You'll Learn

  • Where to find the test in the app.
  • How to place the Testo 405i in a heat exchanger cell.
  • How to run a screening cycle on each cell.
  • What each result means and what it does not mean.
  • What the test cannot tell you.
  • How to finish the report.

Before You Start

  1. Connect the Testo 405i and your clamp meter to measureQuick. See How to Pair Bluetooth Tools.
  2. Place the clamp meter on the blower circuit so it reads blower current.
  3. Check that the furnace has airflow resistance on it, such as the duct system or an evaporator coil. Jim's demonstration furnace had no ductwork, so he set a flow grid on top to add resistance.

Run the Test

  1. In the app, tap Actions, then Quick Tests, then Heat Exchanger Integrity Test. Tap the Info button if you want to read the in-app directions first.
  2. Confirm that the app shows both the Testo 405i and the clamp meter as connected.
    Heat Exchanger Integrity Test setup screen showing probe placement, the connected Testo 405i and Testo 770-3, and the number of heat exchanger cells
  3. Set the number of cells to match the heat exchanger.
  4. Check that the gas burners and inducer are off and the heat exchanger has cooled below 140 °F. Insert the Testo 405i into the first cell, near the cell opening, about 1 to 1.5 inches in and tilted upward. Hold the probe at an angle so the hot-wire opening faces into the cell. Do not lay the probe flat, because air cannot pass through the sensor that way. Keep the probe still.
    Testo 405i hot-wire anemometer with its probe inserted into the first heat exchanger cell of a gas furnace
  5. Tap Start Cell. The app takes a baseline of the air movement in the cell with the blower off.
  6. Turn the blower on. The app marks the moment the blower starts from the clamp meter's current reading.
  7. Wait while the app tells you to. It watches blower current until the blower reaches a steady speed. An ECM blower takes longer to ramp up than a PSC blower.
  8. When the app tells you to, turn the blower off. The app takes a second baseline.
  9. When the reading has settled, tap Finish cycle. The app shows the result for that cell.
  10. Tap Save, move the probe to the next cell, and repeat steps 4 to 9 for every cell.

Reading the Result

When the cycle ends, the app shows the before, blower-on, and after air velocity, and suggests a finding from the trace. Select the screening finding for the cell and add notes if needed. The screen states that results identify where to investigate; they do not confirm a crack, establish tightness, or certify safe operation.

  • Blower-related response detected - inspect further: The air in that cell moved with the blower. Inspect that cell closely.
  • No blower-related response detected: The test did not see air movement that tracked the blower. This result does not clear the heat exchanger. Finish the inspection in AHRI Guideline X.
  • Inconclusive - repeat / inspect: The trace was not clear enough to call. Repeat the cycle or inspect the cell.

In the example above, from a bench demonstration, air velocity in the cell rose with the blower and returned near baseline. In the example below, from the next cell, blower current climbs while the air velocity trace stays flat.

Small, brief changes in the air reading that do not track the blower can come from room air moving in the cell. The app compares the cell reading with blower current and the two baselines.

Limits of the Test

  • The test is a screening. You find and confirm a defect by inspection.
  • The test reports air movement in a cell. It does not identify a defect or its size.
  • A finding of no blower-related response does not mean the heat exchanger has no defect.
  • AHRI Guideline X covers induced draft furnaces.
  • AHRI Guideline X notes that furnace heat exchanger joints are not hermetically sealed, so a small amount of leakage can occur. A blower response is a reason to inspect the cell, not a finding by itself.

The Report

  1. After the last cell, tap Save and Create Report.
  2. Enter what you found by visual inspection and your recommendation. The test identifies the cell to inspect. You confirm any defect by visual inspection, and the report documents what was found and how it was found.
  3. Have the customer sign, then add the technician signature.
  4. Tap Save and Generate Report.

The report lists the tools used, the result for each cell, an explanation of what the screening shows, and your notes and recommendation.

Video

Watch the demonstration: HITMAN™: Know Which Heat Exchanger Cell to Inspect. In it, Jim uses a new furnace with a screw hole drilled in one heat exchanger cell, and a flow grid on top to stand in for ductwork.

Still need help? Email support@measurequick.com.