Adjustable Parameters in measureQuick

Adjustable Parameters in measureQuick

What You'll Learn

  • Which system profile parameters you can adjust and where to find each one in the app
  • How Design Airflow (CFM/ton) changes diagnostic targets based on climate and duct design
  • How SEER rating drives CTOA (Condensing Temperature Over Ambient) and why a wrong SEER produces false charge diagnoses
  • When to override default subcooling and superheat targets with manufacturer-specified values
  • How metering device selection (TXV vs piston) changes the entire diagnostic approach
  • How refrigerant type selection affects all saturation temperature calculations
  • What happens when each parameter is set incorrectly, and how to recognize the symptoms

What You'll Need

  • Device: iPhone (iOS 15+) or Android phone (Android 10+) with measureQuick installed
  • Account: Logged in with an active measureQuick account
  • Context: A project with a system profile configured (or Demo Mode enabled for practice)
  • Knowledge: Understanding of superheat and subcooling (see Superheat & Subcooling) and how to build a manual system profile (see Manual Equipment Profile)
  • Reference: Manufacturer data plate or installation manual for the equipment you are testing
  • Time: 15 minutes to read; practice adjusting parameters in Demo Mode before field use

The Concept

Every diagnostic calculation in measureQuick depends on the system profile. The profile tells the app what kind of equipment is installed, how it was designed to operate, and what targets to evaluate against. When the profile is accurate, the diagnostics are accurate. When it is wrong, the diagnostics are wrong.

There are a small number of adjustable parameters in the system profile and diagnostic screens. Each one controls a specific part of the diagnostic math. This article covers each parameter: what it does, where to find it, what the default is, when to change it, and what goes wrong if it is set incorrectly.

Getting these parameters right matters. As Jim Bergmann explains: "the design temperature difference or condenser temp over ambient was ambient plus 30 degrees" for older equipment, but modern high-SEER systems operate at lower temperature differences. From the mQ V12 database of 115,706 quality-filtered cooling tests, 56.0% of piston systems fail the charge evaluation. Some portion of those failures reflect genuinely undercharged or overcharged systems, but incorrect profile parameters (wrong SEER, wrong metering device, wrong refrigerant) also contribute to false diagnoses.


Parameter 1: Refrigerant Type

What it controls

Refrigerant type determines the pressure-temperature (P/T) relationship curve used for all saturation temperature calculations. Every superheat and subcooling value in the app depends on this setting.

Where to find it

In the system profile setup screen. Refrigerant type is one of the first fields you set when creating or editing a profile.

📷 System profile screen with refrigerant type selector showing available options

Default

No default. You must select the refrigerant type for the system you are testing.

Common values

Refrigerant Typical Application
R410A Standard residential A/C and heat pumps (2010-present)
R22 Legacy systems (pre-2010 installs, declining in field)
R454B Newer replacement for R410A (2025+)
R32 High-efficiency systems, common in ductless/mini-splits

When to change it

Always confirm the refrigerant type matches the equipment data plate. Do not assume R410A on every system. R22 systems are still in service, and R454B is entering the market.

What happens if it is wrong

Every saturation temperature calculation will be incorrect. Superheat and subcooling readings will be off by several degrees, sometimes by 10F or more. The app will flag charge faults that do not exist, or miss real charge problems. This is the single most damaging parameter to get wrong.

Tip: Check the outdoor unit data plate. The refrigerant type is printed there. If the system has been converted (for example, R22 to a drop-in replacement), confirm what refrigerant is actually in the system, not what the data plate says.


Parameter 2: Tonnage

What it controls

System capacity in tons. Tonnage feeds the airflow target calculation: the app multiplies tons by your CFM/ton setting to determine how much airflow the system needs.

Where to find it

In the system profile, under equipment specifications. If you use the AI System Profiler (see D1), it reads tonnage from the model number. If you build the profile manually, you enter it directly.

📷 System profile showing tonnage field

Default

Populated from the model number when using the AI Profiler. No default for manual entry.

Common values

Residential systems: 1.5, 2, 2.5, 3, 3.5, 4, 5 tons.

When to change it

Verify the tonnage matches the actual equipment. Pay attention to oversized evaporator configurations: a 3-ton condenser paired with a 3.5-ton evaporator coil is a 3-ton system for diagnostic purposes (the condenser sets the capacity). See High Efficiency/Oversized Evaporator for these scenarios.

What happens if it is wrong

Airflow targets scale directly with tonnage. A 3-ton system at 400 CFM/ton expects 1,200 CFM. If you enter 2 tons, the app expects 800 CFM. Your airflow diagnostics will be incorrect, which cascades into capacity calculations and the Vitals Score.


Parameter 3: Design Airflow (CFM/ton)

What it controls

The airflow rate per ton of cooling capacity used to calculate the system's target CFM. This is the design intent for the duct system, not a measured value.

Where to find it

In the system profile. Look for the Design Airflow or CFM/ton field. In the Brian Feenie demo walkthrough, this appears at approximately 6:15 on the system profile screen.

📷 System profile screen showing Design Airflow (CFM/ton) setting

Default

400 CFM/ton.

Range

300-500 CFM/ton.

When to change it

Adjust based on climate and system design:

Climate/Condition Recommended CFM/ton Reason
Hot and humid (Gulf Coast, Southeast) 350 CFM/ton Lower airflow drops supply air temperature, increasing dehumidification
Moderate/mixed 400 CFM/ton Standard design assumption for most residential systems
Hot and dry (Southwest, arid) 425-450 CFM/ton Higher airflow maximizes sensible cooling where humidity is not a concern
Manufacturer-specified Per spec Some equipment manuals specify a CFM/ton value; use it

What happens if it is wrong

The app calculates target airflow as: Target CFM = Tonnage x CFM/ton.

If CFM/ton is set too high, the app expects more airflow than the system was designed to deliver. The airflow subsystem will flag a false failure. If CFM/ton is set too low, the app will accept inadequate airflow as passing.

The airflow target also feeds into superheat and subcooling target calculations. Wrong airflow assumptions compound into wrong charge diagnostics.

Tip: When in doubt, leave it at 400 CFM/ton. This is the industry standard assumption and produces reasonable diagnostics for the majority of residential systems. Only adjust it when you have a specific reason.


Parameter 4: SEER Rating

What it controls

The Seasonal Energy Efficiency Ratio of the system. In measureQuick, the SEER rating drives the CTOA (Condensing Temperature Over Ambient) calculation. Higher SEER equipment operates with a lower temperature difference between the condensing temperature and the outdoor ambient air.

Where to find it

In the system profile, under Efficiency Standard. In the demo walkthrough, this appears at approximately 6:17. You select a SEER range, and the app shows the corresponding CTOA.

📷 System profile showing SEER/Efficiency Standard selection with corresponding CTOA displayed

Default

Varies by system. The AI Profiler attempts to determine SEER from the model number. For manual profiles, you select it.

SEER-to-CTOA relationship

SEER Range CTOA
6-9 SEER (Older than 1991) 30.0 F
10-12 SEER (1992-2005) 25.0 F
13-16 SEER (2006-present) 20.0 F
17+ SEER (2006-present) 15.0 F

These are the four discrete buckets the app uses. CTOA is the expected difference between the condensing temperature (saturation temperature at the high-pressure side) and the outdoor ambient temperature. A 10-12 SEER system running with 95F outdoor air should have a condensing temperature around 120F. A 17+ SEER system in the same conditions should condense around 110F.

When to change it

Set SEER to match the outdoor unit's rated efficiency. This is printed on the data plate or available from the manufacturer's specifications. Do not guess. If you cannot determine the SEER rating, err toward the lower end (13-14 SEER for older equipment, 14-16 for post-2015).

What happens if it is wrong

Wrong SEER means wrong CTOA. Wrong CTOA shifts the expected condensing temperature. This directly affects the subcooling calculation and the charge diagnostic.

Example: A 20 SEER system has a real CTOA of about 18F. If you set the profile to 13 SEER (CTOA 30F), the app expects a condensing temperature 12F higher than reality. The app will interpret the actual (correct) condensing temperature as too low and may flag an undercharge that does not exist.

This is one of the most common sources of false charge diagnoses in the field.


Parameter 5: CTOA (Condensing Temperature Over Ambient)

What it controls

The expected temperature difference between the condensing saturation temperature and the outdoor ambient air temperature. CTOA is the bridge between efficiency rating and charge diagnostics.

Where to find it

In the system profile, linked to the SEER selection. When you select a SEER range, the app calculates and displays the corresponding CTOA. On the demo walkthrough, this appears at approximately 6:21.

📷 System profile showing SEER selection with auto-populated CTOA value

Default

Derived from the SEER rating you select. See the SEER-to-CTOA table above.

When to change it

In most cases, let the SEER selection drive the CTOA automatically. Only override the CTOA directly if you have manufacturer documentation that specifies a different CTOA for the exact unit you are testing. Some manufacturers publish CTOA values in their engineering data that differ slightly from the SEER-based approximation.

What happens if it is wrong

Same impact as wrong SEER: the expected condensing temperature shifts, producing incorrect subcooling targets and false charge diagnoses. If the CTOA is too high, the app expects a higher condensing temperature and may miss an overcharge. If the CTOA is too low, the app expects a lower condensing temperature and may flag a false undercharge.


Parameter 6: Metering Device

What it controls

The type of metering device in the system determines the primary diagnostic approach for refrigerant charge evaluation. As Jim Bergmann demonstrates in his walkthrough: "I set the type of metering device - thermostatic expansion valve, piston, capillary tube, electronic expansion valve, or automatic expansion valve." measureQuick supports all five types, though residential systems are predominantly TXV or piston.

  • TXV (Thermostatic Expansion Valve): The app evaluates charge primarily through subcooling. TXV systems regulate superheat mechanically, so superheat is less useful as a charge indicator.
  • Piston / Fixed Orifice: The app evaluates charge primarily through superheat. With a fixed-size orifice, superheat responds directly to charge level.

Where to find it

In the system profile, under Metering Device. In the demo walkthrough, this appears at approximately 6:23.

📷 System profile showing metering device selection - TXV or Fixed Orifice/Piston

Default

No default. You must select the metering device type for the system.

When to change it

Always match the actual metering device in the system. Check the indoor coil (evaporator) data plate or installation documentation. If you see a TXV body on the liquid line entering the evaporator coil, select TXV. If there is no TXV and the system uses a piston or capillary tube, select Fixed Orifice/Piston.

What happens if it is wrong

Setting TXV when the system has a piston means the app evaluates charge by subcooling and largely ignores superheat as a charge indicator. On a piston system, subcooling alone does not reliably indicate charge state, so the app may miss a charge problem.

Setting piston when the system has a TXV means the app evaluates charge by superheat. A functioning TXV actively controls superheat, so the superheat will appear normal regardless of charge level, and the app will report the charge as acceptable when it may not be.

This parameter changes the entire diagnostic logic. Getting it wrong can produce a clean diagnostic report on a system with a significant charge problem.

Tip: When in doubt, physically inspect the evaporator coil. A TXV has a sensing bulb clamped to the suction line near the evaporator outlet. A piston system has no bulb; the metering device is inside the coil distributor.


Parameter 7: Subcooling Target

What it controls

The expected subcooling value for the system, in degrees Fahrenheit. Subcooling is the temperature difference between the actual liquid line temperature and the condensing saturation temperature. The target represents proper charge level for TXV-equipped systems.

Where to find it

In the system profile under charge parameters. In the demo walkthrough, charge parameters appear at approximately 6:35.

📷 System profile showing subcooling target field

Default

Varies by equipment. The app uses a standard default based on the system profile. Typical residential defaults fall in the 8-14F range.

When to change it

Change it when you have the manufacturer's specified subcooling target for the exact condenser you are testing. This is printed on the condenser data plate or in the installation manual. Common manufacturer targets:

Manufacturer/Situation Typical Subcooling Target
Most residential condensers 10-12F
Some Carrier/Bryant models 8-10F
Some Lennox models 12-14F
Per data plate Use the exact value printed

Always use the manufacturer's specified value when available. It accounts for the specific condenser coil design and intended refrigerant volume.

What happens if it is wrong

If the subcooling target is set too high, the app expects more subcooling than the system is designed to produce. A properly charged system will appear undercharged, and a technician following the diagnostics will add refrigerant, overcharging the system.

If the subcooling target is set too low, the app accepts less subcooling than the system needs. An overcharged system may appear acceptable.

Each degree of subcooling target error shifts the charge diagnostic by roughly one degree of measurement tolerance. A 3-4F error in the target can flip a pass to a fail or vice versa.


Parameter 8: Superheat Target

What it controls

The expected superheat value for the system, in degrees Fahrenheit. For piston/fixed orifice systems, superheat is the primary charge indicator. For TXV systems, superheat is controlled by the valve and is less relevant to charge diagnostics.

Where to find it

In the system profile under charge parameters, near the subcooling target.

📷 System profile showing superheat target field

Default

For piston systems, the app calculates the target superheat from operating conditions: outdoor ambient temperature and indoor wet bulb temperature. This is the standard charging chart method. The calculated target typically falls between 5F and 25F depending on conditions.

For TXV systems, the app uses a nominal superheat reference (typically 10-12F) since the TXV controls superheat mechanically.

When to change it

For piston systems, the calculated target is usually correct. Override it only if the manufacturer publishes a specific superheat target that differs from the standard charging chart calculation for the conditions you are testing in.

For TXV systems, superheat adjustment is rarely necessary because the TXV regulates it independently of charge level.

What happens if it is wrong

On a piston system, a wrong superheat target produces the same kind of cascade as a wrong subcooling target: the charge diagnostic evaluates against the wrong benchmark, and the pass/fail result may not reflect actual charge state.

On a TXV system, the superheat target has less diagnostic impact because charge is evaluated through subcooling. However, a significantly wrong superheat target can still affect supplementary diagnostic flags.


Parameters Quick Reference

Parameter Location Default Typical Range When to Adjust Risk if Wrong
Refrigerant Type System Profile None (must select) R410A, R22, R454B, R32 Always verify against data plate All saturation temps wrong; false charge diagnosis
Tonnage System Profile From model number (AI) or manual entry 1.5-5 tons Verify against data plate; use condenser rating for oversized evap Airflow targets and capacity calculations wrong
Design Airflow (CFM/ton) System Profile 400 300-500 Humid climate: 350; dry climate: 450; per manufacturer spec Airflow pass/fail and charge targets shift
SEER Rating System Profile (Efficiency) Varies 13-25+ Match outdoor unit rated efficiency Wrong CTOA; false charge diagnosis
CTOA Derived from SEER Auto-calculated 15-30F Only if manufacturer specifies a different CTOA Expected condensing temp shifts; charge diagnosis wrong
Metering Device System Profile None (must select) TXV or Piston/Fixed Orifice Always match actual equipment Entire diagnostic approach wrong; misses real charge faults
Subcooling Target Charge Parameters 8-14F (varies) 8-14F When manufacturer data plate specifies a target Over/undercharge diagnosis off by target error margin
Superheat Target Charge Parameters Calculated from conditions (piston) 5-25F Rarely; only if manufacturer specifies differently Piston charge diagnosis off; less impact on TXV systems

How Parameters Interact

These parameters do not work in isolation. They form a chain of dependent calculations:

  1. Refrigerant Type sets the P/T curve.
  2. SEER/CTOA sets the expected condensing temperature relative to outdoor ambient.
  3. Metering Device determines whether the app evaluates charge through subcooling (TXV) or superheat (piston).
  4. Subcooling/Superheat Targets set the specific benchmarks within that diagnostic approach.
  5. Tonnage x CFM/ton sets the airflow target, which feeds back into charge calculations.

Getting any single parameter wrong shifts the diagnostic output. Getting two or more wrong can produce results that appear internally consistent but are entirely misleading. This is why profile verification (see Profile Verification) is a critical step before interpreting diagnostics.


Video Walkthrough

  • YouTube (HVAC School): (18,030 views, 1:55). Covers how compression ratio, capacity, and efficiency interact with system profile parameters. Includes discussion of static pressure, refrigerant behavior, airflow, and system profiling

  • YouTube (HVAC School): (15,014 views, 1:41). Common charging errors that result from incorrect profile parameters, covering refrigerant selection, metering device, system profiling, and probe placement

  • YouTube: (4,695 views, 9:22). Explains how parameters feed into the diagnostic calculations and what the app does with each setting

  • YouTube: (9,324 views, 18:40). Demonstrates parameter adjustment for high-efficiency systems where SEER, CTOA, and CFM/ton deviate from standard residential defaults

  • YouTube: (18,992 views, 53 min). Jim Bergmann discusses parameter tuning for accurate diagnostics, including CTOA selection and metering device implications

  • YouTube: (15,726 views, 45 min). End-to-end commissioning walkthrough that includes system profile setup and parameter selection


Tips & Common Issues

Diagnostics show a charge fault, but the system seems fine

Check your SEER rating and CTOA first. This is the most common cause of false charge flags. If the SEER is set too low for a high-efficiency system, the app expects a higher condensing temperature than the system actually produces. Correct the SEER, and the charge diagnostic will update.

System profile was auto-detected by the AI Profiler, but results still look wrong

The AI Profiler reads the model number from a photo. It correctly identifies tonnage and refrigerant type in most cases, but it may not always determine the exact SEER rating or metering device type. Verify those two parameters manually after the profiler runs. See Profile Verification.

I do not know the SEER rating

Check the outdoor unit data plate. If it only lists EER (not SEER), you can approximate: SEER is typically 1.1-1.2x the EER for single-stage equipment. If the data plate is unreadable, look up the model number on the manufacturer's website or the AHRI directory (ahridirectory.org). As a last resort, estimate based on equipment age: pre-2006 equipment is likely 10-13 SEER; 2006-2015 is likely 13-16 SEER; post-2015 is likely 14-20+ SEER.

I cannot tell if the system has a TXV or piston

Physically inspect the liquid line where it enters the evaporator coil. A TXV has a valve body (brass or steel, larger than the liquid line) and a sensing bulb clamped to the suction line near the evaporator outlet, usually insulated with tape or foam. A piston system has no external valve body; the metering device is a small brass fitting or disc inside the coil's distributor assembly. If you still cannot determine the metering device, check the evaporator coil's model number and look up the specifications.

The app calculated a superheat target that seems too high or too low

For piston systems, the calculated superheat target depends on outdoor ambient temperature and indoor wet bulb temperature. Verify that both of these readings are accurate. If the outdoor temperature probe is in direct sunlight or near the condenser discharge air, it will read high and shift the superheat target. If the indoor wet bulb reading is incorrect (probe not in the airstream, or in a dry location), the target calculation will be off.

When should I adjust CFM/ton below 400?

When the system is installed in a hot, humid climate where the design intent is to maximize dehumidification. Lowering CFM/ton drops the supply air temperature, pulling more moisture out of the air. Common in the Gulf Coast states, Florida, and similar climates. Some equipment manufacturers specify 350 CFM/ton for their humidity-optimized systems. Do not drop below 300 CFM/ton; this risks evaporator coil icing.

Multiple parameters seem wrong at once

Start with refrigerant type. Confirm it is correct, then move to metering device, then SEER/CTOA, then airflow. Fix them in that order, because each downstream parameter depends on the ones above it.


Related Articles

Prerequisites (complete these first):

Follow-up articles (next steps after this one):

Related in the same domain:


Need Help?

If you get stuck or this article does not answer your question:

  • Check the Related Articles section above
  • Contact measureQuick support: support@measurequick.com
    • Related Articles

    • Connecting Sensorcon CO Meters to measureQuick

      What You'll Learn Which Sensorcon CO meter models are compatible with measureQuick How to pair a Sensorcon meter with measureQuick via Bluetooth Where the CO reading appears in the measureQuick app CO safety thresholds and the action required at each ...
    • Installing the measureQuick App

      What You'll Learn Which devices and operating systems are supported How to install measureQuick from the App Store (iOS) or Google Play (Android) Which app permissions to enable and why each one matters How to log in after your first launch How to ...
    • Creating Your measureQuick Account

      What You'll Learn How to download the measureQuick app on iOS or Android How to create a personal account with email and password How to complete email verification What to expect on first login How to navigate the home screen after account creation ...
    • Superheat & Subcooling in measureQuick

      What You'll Learn How measureQuick calculates superheat and subcooling from your probe data Which metric to target based on the metering device type in your system profile How target superheat is derived from outdoor ambient and return air wet bulb ...
    • Equipment Types in measureQuick

      What You'll Learn Which equipment types measureQuick supports and how the app classifies them Which Guided Workflow to select for each equipment type How profile settings differ between split systems, package units, heat pumps, and gas furnaces How ...