This guide answers "how do I test a mini split system" in measureQuick: which workflow to choose, where the probes go, and how to read the results. It applies to mini split, multi split, ductless, and VRF systems.
Mini-splits do not test like ducted systems: there is no liquid line at the head, superheat runs near zero, and the indoor unit gets its power from the outdoor unit. measureQuick has a dedicated mini-split workflow that accounts for all of this. Set it up right and the system will take longer to stabilize than the test takes to run.
Select the Mini-Split/Multi-Split/VRF workflow when starting your project. It is listed with the Classic Workflows; see the Workflow Comparison and Usage Guide. In your project details, set the equipment type to mini-split.
Mini-splits have many operating modes and you rarely know how the unit is rated, so force it to run continuously the way it was designed to run:
Activate your probes in the Toolbox before you start filling out the project so they stabilize while you work.
Do not look for a liquid line. On a mini-split the metering device is in the outdoor unit, so both lines at the indoor head run cold. The small line is not a liquid line and there are no prescribed temperatures for it. You only measure the suction side.
The indoor heads are fed by the outdoor unit, so you capture electrical readings once, at the outdoor unit. You do not measure each head independently.
A few things that look wrong on a mini-split are normal:
A green flag means the system is in the ballpark and running to its capacity. When you are done, save the data and exit with sync to cloud so the project is stored to your measureQuick cloud account.
Questions about a specific reading? Email support@measurequick.com with the project synced to the cloud so we can look at your data.