The type of metering device installed in the system determines which measurement is your primary charge indicator. This is not a preference; it is how the physics works.
measureQuick handles this automatically. When you profile the system and select the metering device type, the app adjusts its target ranges and diagnostic logic accordingly. As Jim Bergmann explains when walking through the profile setup: "I set the type of metering device - thermostatic expansion valve, piston, capillary tube, the electronic expansion valve, or automatic expansion valve." The metering device selection directly controls which charge indicator measureQuick prioritizes.
On a fixed orifice system, the metering device is a simple restriction (a brass plug with a calibrated hole, or a short capillary tube). It does not adjust to changing conditions. The amount of refrigerant that flows through it depends on the pressure difference across it.
This means superheat responds directly to charge level:
| Measurement | Direction | Explanation |
|---|---|---|
| Superheat | Low (below target) | Excess refrigerant floods the evaporator; not enough heat to superheat it all |
| Subcooling | High (above target) | Excess liquid refrigerant backs up in the condenser |
| Suction pressure | High | More refrigerant in the evaporator raises the boiling pressure |
| Head pressure | High | More liquid in the condenser raises condensing pressure |
| Suction line temperature | Cold (may sweat or frost) | Refrigerant is not fully superheated leaving the evaporator |
What it looks like in measureQuick: Superheat reads below the target zone (green range). The superheat indicator turns yellow or red on the low side. Subcooling reads above the target zone. The diagnostics may flag "possible overcharge" or "low superheat."
measureQuick diagnostics screen on a piston system showing low superheat, high subcooling, with charge indicators flagged
| Measurement | Direction | Explanation |
|---|---|---|
| Superheat | High (above target) | Insufficient refrigerant evaporates early; the remaining vapor superheats excessively |
| Subcooling | Low (below target) | Not enough liquid refrigerant reaches the condenser |
| Suction pressure | Low | Less refrigerant in the evaporator drops the boiling pressure |
| Head pressure | Low | Less refrigerant in the condenser drops the condensing pressure |
| Suction line temperature | Warm | Excessive superheat warms the suction line |
What it looks like in measureQuick: Superheat reads above the target zone. The superheat indicator turns yellow or red on the high side. Subcooling reads below the target zone. The diagnostics may flag "possible undercharge" or "high superheat."
measureQuick calculates the target superheat based on the outdoor ambient temperature, return air wet bulb, and the equipment profile. The allowable range is typically plus or minus 5 degrees F from the calculated target. As Jim Bergmann notes: "it's a plus or minus 5 degrees of superheat, so we look at 5 degrees of saturation, that's an allowable range."
A thermostatic expansion valve actively modulates the refrigerant flow to maintain a set superheat at the evaporator outlet. The sensing bulb on the suction line controls the valve opening. When superheat rises, the valve opens more. When superheat drops, the valve closes.
Because the TXV regulates superheat, superheat stays relatively stable regardless of charge level (within the TXV's operating range). The charge condition shows up in subcooling instead:
| Measurement | Direction | Explanation |
|---|---|---|
| Superheat | Near target (TXV compensates) | The TXV closes down to prevent flooding, but superheat stays controlled |
| Subcooling | High (above target) | Excess refrigerant collects as liquid in the condenser |
| Head pressure | High | More liquid in the condenser raises condensing pressure |
| Suction pressure | May be slightly high | TXV may not fully compensate for excess charge |
What it looks like in measureQuick: Subcooling reads above the target zone. The subcooling indicator turns yellow or red on the high side. Superheat may remain in or near the acceptable range because the TXV is compensating. This is why subcooling is the indicator to watch.
| Measurement | Direction | Explanation |
|---|---|---|
| Superheat | Near target initially, then rises | The TXV opens fully but cannot get enough refrigerant; eventually superheat climbs |
| Subcooling | Low (below target) | Not enough liquid refrigerant in the condenser |
| Head pressure | Low | Insufficient refrigerant reduces condensing pressure |
| Suction pressure | Low | The TXV starves trying to maintain superheat |
What it looks like in measureQuick: Subcooling reads below the target zone. The subcooling indicator turns yellow or red on the low side. On a severely undercharged TXV system, superheat will also rise because the valve is fully open and still cannot supply enough refrigerant.
Typical subcooling targets range from 8 to 15 degrees F, depending on the manufacturer's specification. measureQuick uses the equipment profile to determine the target. When you profile the system as having a TXV, the app shifts its primary charge evaluation to subcooling.
measureQuick's V12 database of 115,706 quality-filtered cooling tests reveals that 56.0% of piston systems fail the charge evaluation. This is the charge failure rate after data quality filtering, on systems where airflow and other conditions were assessed.
This number is high, and it reflects the real condition of the installed base. More than half of the piston systems tested by measureQuick users had a detectable charge problem. The reasons include:
These are not edge cases. This is the state of the residential HVAC installed base.
measureQuick records a pass/fail result for charge in the pf_charge field. This evaluation uses the following logic:
A Pass means the primary charge indicator is within the acceptable range for the metering device type and operating conditions.
A Fail means the primary charge indicator is outside the acceptable range. The measurement record captures the actual values so you can see how far outside the range the system is.
The pf_charge_override field indicates whether the technician manually changed the pass/fail result. An override of 1 means the technician disagreed with the automated evaluation and changed it. This might happen when the technician knows about a condition (such as a restricted TXV) that explains the reading.
Before concluding that a system has a charge problem, confirm:
YouTube: - Jim Bergmann demonstrates how measure quick evaluates charge on both piston and TXV systems, explaining: "we record the superheat of the sub cooling, primarily on a TXV system we'll record a sub cooling because there's a range."
YouTube: (21:52) - Complete charging procedure with measurement interpretation for both metering device types
YouTube: (9:22, 4,695 views) - Explains the diagnostic logic measureQuick uses to evaluate system performance, including how charge indicators are assessed
YouTube: - Jim Bergmann walks through the full app, including how profiles and metering device selection affect charge target calculations
On a piston system, superheat is primary, but subcooling still provides useful information. If superheat is within the target range but subcooling is elevated, the system may be slightly overcharged but not enough to push superheat out of range. It can also indicate a partially restricted condenser or a dirty condenser coil. Check condenser airflow and coil condition.
Very low or zero subcooling on a TXV system is a strong indicator of significant undercharge, a major refrigerant leak, or a restriction in the liquid line before the TXV. This condition starves the TXV. The system needs a leak check before adding refrigerant.
In cooling mode, a heat pump uses the same charge evaluation as a standard A/C: the indoor metering device type determines the primary indicator. In heating mode, the outdoor metering device type applies. measureQuick handles this automatically when you select the correct mode and profile.
A passing charge evaluation means the refrigerant side is within the acceptable range. Poor cooling with a passing charge usually points to an airflow problem, an oversized or undersized system, duct leakage, or a building envelope issue. Check TESP, CFM per ton, and the temperature split (return minus supply dry bulb).
CTOA stands for Condenser Temperature Over Ambient. It is the difference between the condensing (saturation) temperature and the outdoor ambient temperature. Typical design CTOA is about 30 degrees F. An elevated CTOA with normal subcooling may indicate a dirty condenser or non-condensable gases in the system. measureQuick calculates and displays CTOA as part of the diagnostic screen.
Prerequisites (complete these first):
Follow-up articles (next steps after this one):
Related in other domains:
If you get stuck or this article does not answer your question: