A heat pump is an air conditioning system with a reversing valve. In cooling mode, it operates identically to a standard A/C system. In heating mode, the reversing valve switches the direction of refrigerant flow, and the roles of the indoor and outdoor coils swap.
This means measureQuick uses two different workflows for heat pumps depending on the mode:
| Mode | Workflow to Use | Why |
|---|---|---|
| Cooling | AC Install (or AC Service) | Same cycle as A/C. Condenser is outdoors, evaporator is indoors. Probe placement, diagnostics, and pass/fail logic are identical to A/C. |
| Heating | Heat Pump Heating | The cycle is reversed. The outdoor unit becomes the evaporator; the indoor unit becomes the condenser. Probe roles, superheat/subcooling locations, and diagnostic targets all change. |
If you are commissioning a new heat pump installation, you will typically run both workflows: AC Install for cooling mode performance, then Heat Pump Heating for heating mode performance.
Heat pump commissioning demands more technical knowledge than standard A/C commissioning because you must verify performance in both modes. DR Richardson (Owner, Elephant Energy) describes measureQuick as providing "a data-driven methodology and process to ensure we've done that commissioning checklist," noting that paper-based checklists are not data-connected. With heat pump market share at 47% of installations in measureQuick's 2025 data, this workflow is increasingly common.
Open measureQuick and create a new project for this installation.
See Creating Projects for detailed project setup instructions.
New project screen with customer name, address, and date fields
For a new heat pump installation, start with cooling mode. Set the thermostat to call for cooling and allow the system to run.
This is the same workflow described in A/C Installation Workflow. The cooling mode test for a heat pump is identical to an A/C installation test. Follow the G1 procedure for:
Tip: When profiling the equipment, make sure the system type is set to Heat Pump, not Air Conditioner. The equipment type does not change the cooling mode diagnostics, but it ensures the project record correctly identifies this as a heat pump system.
Workflow selection screen showing cooling project types including A/C or Heat Pump Installation
Once the system stabilizes and all diagnostics are evaluated:
This is your "test in" for the cooling mode. See Save Test In / Save Test Out for details on the snapshot process.
Diagnostics screen showing cooling mode results with Save Test In button
Now test the heating mode. Switch the thermostat from cooling to heating. Allow the system to cycle off cooling and start the heating cycle.
Before starting the heating mode test:
The Heat Pump Heating workflow looks similar to the AC Install workflow but with critical differences in how it interprets your measurements.
Workflow selection screen showing Heat Pump Heating Test option in the Heating Projects section
If you already profiled the equipment during the cooling mode test, the app carries forward the equipment identification (manufacturer, model, serial, refrigerant, tonnage). You still need to confirm or set heating-specific profile fields:
Tip: The outdoor metering device may differ from the indoor metering device. In cooling mode, the indoor metering device controls expansion. In heating mode, the outdoor metering device controls expansion. The system profile for heating mode should reflect the outdoor metering device.
This is where heat pump testing differs from A/C testing. In heating mode, the refrigeration cycle reverses:
| Component | Cooling Mode Role | Heating Mode Role |
|---|---|---|
| Outdoor unit | Condenser (rejects heat) | Evaporator (absorbs heat) |
| Indoor unit | Evaporator (absorbs heat) | Condenser (releases heat) |
| Suction line | Returns to compressor from indoor coil | Returns to compressor from outdoor coil |
| Liquid line | Carries liquid from outdoor to indoor | Carries liquid from indoor to outdoor |
What this means for measurements:
measureQuick handles this reversal automatically when you select the Heat Pump Heating workflow. The app knows which probes correspond to evaporator-side and condenser-side measurements based on the workflow selection.
[Diagram] Heat pump refrigerant cycle in heating mode. The outdoor coil acts as the evaporator (absorbing heat from outdoor air), and the indoor coil acts as the condenser (releasing heat into the home). Superheat is measured at the outdoor unit (suction line leaving the outdoor coil), and subcooling is measured at the indoor unit (liquid line leaving the indoor coil). The reversing valve redirects refrigerant flow so that every line's thermal role is swapped compared to cooling mode.
Probe placement changes in heating mode because the coil roles are reversed. See Heat Pump Heating Mode Probes for detailed placement instructions. The summary:
Outdoor unit (now the evaporator):
Indoor unit (now the condenser):
Static pressure probes remain in the same locations as cooling mode (return side and supply side of the air handler).
[Diagram] Heat pump heating mode probe placement. Outdoor unit (evaporator side): suction line temp clamp on the line leaving the outdoor coil, suction pressure at the outdoor service port, outdoor ambient sensor 3-5 ft from unit. Indoor unit (condenser side): liquid line temp clamp on the line leaving the indoor coil, discharge/liquid pressure at the indoor side, supply air temp in the supply plenum, return air temp in the return plenum. Static pressure probes remain in the same duct locations as cooling mode.
Tip: If you left probes in place from the cooling mode test, you may need to physically move the suction line probe. In cooling mode, the suction line is at the indoor coil. In heating mode, the suction line is at the outdoor coil. The liquid line probe may also need to move depending on your setup.
The Heat Pump Heating workflow presents a guided checklist similar to the AC Install workflow. Work through each section:
Wait for the system to stabilize before evaluating diagnostics. Heating mode stabilization typically takes 10-15 minutes of continuous operation. As the Part 4 video demonstrates, use the stabilization wait productively: "pay attention to during this test while we wait for the system to stabilize, let's go ahead and get our meter connected to Bluetooth." See System Stabilization.
The Diagnostics screen in heating mode displays the same pass/fail indicators as cooling mode, but the underlying calculations reflect the reversed cycle:
| Diagnostic | What It Evaluates in Heating Mode |
|---|---|
| Superheat | Measured at the outdoor unit (evaporator). Compared against the target for current outdoor ambient conditions. |
| Subcooling | Measured at the indoor unit (condenser). Compared against the manufacturer's specified target. |
| TESP | Total External Static Pressure remains the same measurement (return + supply static). |
| Supply air temp | Should be warm (typically 90-120 F depending on system capacity and outdoor conditions). |
| Temperature split | Difference between return and supply air. In heating mode, supply should be warmer than return. |
Review each diagnostic. Tap any indicator to open the detail screen and see the measured value, target, and acceptable range.
Once the system has stabilized and you have reviewed all diagnostics:
For a new installation, both tests together document the full commissioning of the heat pump in both operating modes.
Project view showing two saved tests, one cooling mode and one heating mode
Heat pumps in heating mode periodically run defrost cycles to melt ice that accumulates on the outdoor coil. During defrost, the system temporarily switches back to cooling mode (the reversing valve actuates) to send hot gas through the outdoor coil.
What happens during defrost:
Do not save a test during a defrost cycle. Wait for defrost to complete and the system to return to steady heating operation. You will know defrost is over when:
Allow an additional 5-10 minutes after defrost ends before evaluating diagnostics or saving the test.
Variable-speed (inverter-driven) heat pumps adjust compressor speed to match the heating load. This affects testing:
Tip: If the system does not have a test mode and outdoor conditions are mild, the compressor may run at minimum speed. Document the operating conditions (outdoor temp, compressor speed if displayed) alongside the test results. A commissioning test at part load is still valuable; note the conditions in the project.
Heat pump systems often include auxiliary heat strips (electric resistance) or a backup furnace (dual fuel). These activate when:
During a heat pump heating mode test:
Jim Bergmann describes the heat pump heating workflow process in his Part 4 walkthrough: "workflows for heat pump heating operation, not the non-invasive test, rather the gauge-up test, so we're going to be gauging up... installed the system in heat pump heating mode, we can simply do a test, but every OEM will tell you that the proper way to commission" requires the full gauge-up approach.
On using wait time productively during stabilization: "pay attention to during this test while we wait for the system to stabilize, let's go ahead and get our meter connected to Bluetooth." This approach - completing ancillary tasks during the stabilization period - keeps the workflow efficient without rushing measurements.
From the Heat Pump Commissioning Standards discussion, Jim notes the growing importance of this workflow: "your homeowner decides they want to put a heat pump in, or you talk them into a heat pump, even if they have a heat pump, let's say they have a heat pump..." With heat pump market share at 47% of installations in measureQuick's 2025 data, proper commissioning in both modes is a baseline skill.
DR Richardson (Owner, Elephant Energy) describes measureQuick as providing "a data-driven methodology and process to ensure we've done that commissioning checklist," noting that paper-based checklists are not data-connected. This is particularly relevant for heat pump installations where both cooling and heating mode results must be documented.
Michael Housh (Owner, Housh Home Energy): "Our new installation callbacks have been reduced. We're not having to go back later to resolve issues." He credits the guided workflow structure with ensuring no commissioning steps are skipped, which is especially important when commissioning both modes on a heat pump.
Tevis DesChamp (Owner, Fire and Ice Refrigeration): "Two new guys did about 50 calls their first month with no callbacks and eight or nine five-star reviews." His company uses measureQuick to get entry-level technicians running heat pump service calls within three to four months.
YouTube: (13 min). The primary reference for this article. Walks through the heat pump heating gauge-up test workflow from start to finish, including airflow adjustments after commissioning, probe deployment, and stabilization. Covers both the non-invasive and full gauge-up test approaches, noting that "every OEM will tell you that the proper way to commission" requires the full gauge-up test
YouTube: (80 min, HVAC Design Partners). In-depth discussion on heat pump commissioning standards, including real-world examples of TrueFlow testing on existing systems and the business case for proper commissioning
YouTube: (21,950 views, 1:41). Short demonstration of where to place probes when the heat pump is running in heating mode
YouTube: (1,390 views, 8 min). Covers non-invasive and full diagnostic approaches for heat pump heating mode
YouTube: (14 min). Detailed walkthrough of all heating workflows in measureQuick, including heat pump heating mode
YouTube: (9,324 views, 18:40). Covers variable-speed compressor testing, profiling, and diagnostic interpretation
YouTube: (4:00). Demonstrates how to start a heat pump heating and cooling project from the cloud, including loading existing equipment profiles and saving data. Jim Bergmann: "I'm going to tap on AC heat pump heating and cooling and I'm just going to start this from the cloud."
The AC Install workflow assumes the outdoor unit is the condenser and the indoor unit is the evaporator. In heating mode, those roles are reversed. If you run AC Install while the system is in heating mode, the diagnostic calculations will be wrong: superheat and subcooling will be evaluated at the wrong measurement points, and the pass/fail results will not reflect actual system performance.
Switch to the Heat Pump Heating workflow. You do not need to re-profile the equipment; start a new test with the correct workflow selection.
They are. In cooling mode, superheat is measured indoors (evaporator side) and subcooling is measured outdoors (condenser side). In heating mode, those locations reverse. If you are seeing values that seem backward, confirm you selected the correct workflow (Heat Pump Heating, not AC Install) and that your probes are in the correct heating mode positions.
Check outdoor ambient temperature. Heat pump heating output decreases as outdoor temperature drops. At 40 F outdoor, a heat pump may deliver 100-110 F supply air. At 20 F outdoor, supply air may drop to 85-95 F. This is normal heat pump behavior; the system extracts less heat from colder outdoor air.
If supply air is unusually cold (below 80 F) and the system has been running for 15+ minutes, check for:
Frequent defrost cycles indicate heavy ice buildup on the outdoor coil. Possible causes: low refrigerant charge, dirty outdoor coil, faulty defrost control, or testing at high humidity with near-freezing outdoor temperatures. Wait for each defrost cycle to complete before taking readings. If defrost cycles are more frequent than every 30 minutes, document this as a finding.
If outdoor conditions are too cold for cooling mode testing (below 60 F outdoor), defer the cooling mode test to a warmer day. If outdoor conditions are too warm for heating mode testing (above 65 F outdoor), the heat pump may not sustain heating operation long enough for a valid test. Document what you can and note the outdoor conditions.
In cooling mode, the metering device at the indoor coil (TXV or piston) determines the primary charge indicator. In heating mode, the metering device at the outdoor coil determines the primary charge indicator. Some systems have a TXV indoors and a piston outdoors, or vice versa. Check the manufacturer's installation documentation and set the heating mode profile accordingly.
This is normal. In heating mode, the outdoor unit is the evaporator. Suction pressure is lower than in cooling mode (the system is absorbing heat from potentially cold air), and compressor operation sounds different at lower suction pressures. Louder or higher-pitched compressor noise in heating mode does not necessarily indicate a problem.
The Vitals score (0-100 system quality rating) requires 9 or more physical probe channels connected for cooling and heating modes. If fewer than 9 physical probes are connected, the Vitals score will not calculate. Verify your probe count on the measurement screen before expecting a Vitals result. See Understanding Diagnostic Screens for details on the Vitals score requirements.
Prerequisites (complete these first):
Follow-up articles (next steps after this one):
Related in the same domain:
If you get stuck or this article does not answer your question: