Heat pumps now represent 47% of the residential HVAC market (full-year 2025 data, measureQuick V12 database). Nearly half of the systems technicians encounter can operate in heating mode, and many service complaints occur during winter. If you only test in cooling mode, you miss heating-specific faults: reversing valve leaks, defrost board failures, auxiliary heat staging problems, and low-ambient capacity shortfalls.
Heating mode reverses the refrigerant cycle. The indoor coil, which acts as the evaporator in cooling mode, becomes the condenser. The outdoor coil, which rejects heat in cooling, now absorbs heat from the outdoor air. Every measurement location and diagnostic target changes with this reversal. Selecting the wrong mode in the app produces inverted pass/fail results for every subsystem.
DR Richardson (Owner, Elephant Energy) found that data-driven commissioning and testing in heating mode was critical for Colorado's climate: "Not a single customer lost heat on the coldest night of the decade."
Before opening the app, verify the heat pump is running in heating mode at the equipment.
At the thermostat:
At the outdoor unit:
If you cannot determine the mode by touch, clamp a temperature probe on each refrigerant line at the outdoor unit. The cold line is always the suction side, regardless of mode.
[Visual Reference] Outdoor heat pump unit in heating mode with pipe clamp temperature probes attached. One clamp is on the suction line (the cold line leaving the outdoor coil, carrying low-pressure gas back to the compressor). The other clamp is on the liquid line (the warm line carrying subcooled liquid from the indoor coil to the outdoor metering device). In heating mode, the cold line at the outdoor unit is always the suction side.
Open measureQuick. Create a new project or open the existing project for this customer.
Do not use the A/C or cooling workflow when the system is in heating mode. The heating workflow applies reversed diagnostic targets automatically. If you select the wrong workflow, subcooling and superheat targets, supply/return temperature expectations, and pressure ranges will all be inverted.
Workflow selection screen showing Heat Pump Heating Test in the Heating Projects section
Tip: If you started from the cloud and the system has an existing project, the equipment profile carries forward. Verify the mode is set to Heating before proceeding.
In cooling mode, superheat is measured at the indoor coil (evaporator outlet) and subcooling at the outdoor coil (condenser outlet). In heating mode, those locations swap:
| Parameter | Cooling Mode | Heating Mode |
|---|---|---|
| Evaporator | Indoor coil | Outdoor coil |
| Condenser | Outdoor coil | Indoor coil |
| Superheat measured at | Indoor coil outlet (suction line to outdoor unit) | Outdoor coil outlet (suction line at outdoor unit) |
| Subcooling measured at | Outdoor coil outlet (liquid line) | Indoor coil outlet (liquid line) |
| Expected supply air | Cooler than return | Warmer than return |
The diagnostic logic does not change. Low superheat still means the evaporator is flooded (possible overcharge or TXV stuck open). High superheat still means the evaporator is starved (undercharge, restriction, or low airflow across the evaporator). What changes is which coil is which.
measureQuick handles this reversal automatically when you select the Heat Pump: Heating workflow. The app relabels measurement points and recalculates targets for heating mode. Your job is to place probes on the correct lines and confirm the app is in the right mode.
Probe placement follows the same physical logic as cooling, but the thermal context is reversed.
| Probe | Location in Heating Mode |
|---|---|
| Suction line temp | Line leaving the outdoor coil (cold); this is the evaporator outlet |
| Liquid line temp | Line leaving the indoor coil (warm); this is the condenser outlet |
| Discharge line temp | Compressor discharge line (same location as cooling) |
| Outdoor ambient temp | Shaded area near outdoor unit, 3-5 feet away |
| Supply air temp | First accessible supply register or plenum (should be warm) |
| Return air temp | Return air grille or plenum |
| High-side pressure | Discharge service port (indoor coil side in heating) |
| Low-side pressure | Suction service port (outdoor coil side in heating) |
| Static pressure | Supply and return duct taps (same as cooling) |
You need 9+ physical probes for a valid Vitals Score in heating mode, the same threshold as cooling.
[Diagram] Heating mode probe placement at the outdoor unit and indoor unit. Outdoor (evaporator): suction line temp on the cold line leaving the outdoor coil, discharge line temp on the compressor output, outdoor ambient temp 3-5 ft away in shade, low-side pressure at the suction service port. Indoor (condenser): liquid line temp on the warm line leaving the indoor coil, supply air temp at the first supply register, return air temp at the return plenum, high-side pressure at the discharge service port. Static pressure taps in the supply and return ducts, same positions as cooling mode. 9+ physical probes required for a valid Vitals Score.
Heat pump heating mode requires longer stabilization than cooling mode. Allow 15-20 minutes for readings to settle, compared to 10-15 minutes in cooling.
At lower outdoor temperatures, the compressor works harder and the refrigerant cycle takes longer to reach steady state. Watch the stability indicators on the Diagnostics screen. Do not save Test In or Test Out data until all readings are stable.
Jim Bergmann notes in the measureQuick training series: "It takes about seven to eight minutes to actually get stabilized" under normal conditions, but heating mode in cold weather can take longer.
When outdoor temperatures drop below approximately 40F, the system will periodically enter defrost mode. During defrost:
Do not capture or evaluate readings during a defrost cycle. Wait for defrost to complete, then allow another 5-10 minutes of stabilization before saving data.
If defrost cycles are occurring every 10-15 minutes, that may indicate a defrost board or sensor problem rather than normal operation. Normal defrost intervals range from 30-90 minutes depending on conditions and manufacturer settings.
Once readings are stable, review the Diagnostics screen. Key heating-mode evaluation points:
Refrigerant charge:
Temperature differential:
Airflow:
Save the Test In when you are satisfied that readings are stable and representative.
Note that commissioning (verifying a new installation) should always be done in cooling mode per ACCA and manufacturer standards, because cooling mode provides more accurate charge assessment. Heating mode testing is for service calls and maintenance visits where the system is already in heating operation.
YouTube: (13 min) - Walks through the full heat pump heating gauge-up workflow, including probe deployment and diagnostic evaluation in heating mode
YouTube: (30 min) - Explains why commissioning is done in cooling mode and when heating mode testing is appropriate for service visits
YouTube: (80 min, HVAC Design Partners) - Covers heat pump standards, reversing valve verification, and real-world testing across modes
YouTube: (25 min) - Discusses heat pump heating workflows and hybrid system considerations
Confirm you selected Heat Pump: Heating and not the A/C or cooling workflow. If the workflow mode is wrong, all targets are inverted. Exit the test, create a new one with the correct workflow, and start over.
At low outdoor ambient temperatures, suction pressure drops and superheat increases naturally. This does not always indicate an undercharge. Compare your readings against the manufacturer's heating mode performance tables for the current outdoor temperature. Variable-speed systems may ramp compressor speed to compensate, which affects expected superheat.
Wait for defrost to complete (2-10 minutes), then allow 5-10 minutes of restabilization. If you already saved a Test In during defrost, the data is unreliable. Run a new test after the system returns to steady-state heating.
Check whether auxiliary heat is activating. If it is not, and outdoor temperature is below 25-30F, the heat pump may simply be at the limit of its capacity. This is normal physics, not a fault. If auxiliary heat should be running but is not, check the thermostat staging configuration and the auxiliary heat contactor or relay.
Only if you have reason to suspect a mode-specific fault (reversing valve leak, defrost board failure). For routine maintenance, test in whichever mode the system is currently operating.
Prerequisites (complete these first):
Follow-up articles (next steps after this one):
Related in the same domain:
Contact measureQuick support: support@measurequick.com